Appendix A – Parameter Listings
Installation and Start-up Guide for NPBA-01
A-7
26 MOTOR CONTROL
501
26.1 FLUX OPTIMIZATION
0 = NO; Hex FFFF = YES
502
26.2 FLUX BRAKING
503
26.3 IR COMPENSATION
0 % ... 30 % (effective only when the
SCALAR motor control mode is selected)
1 1 %
30 FAULT FUNCTIONS
601
30.1 AI<MIN FUNCTION
1 = FAULT; 2 = NO; 3 = CONST SP 15; 4 = LAST SPEED
602
30.2 PANEL LOSS
1 = FAULT; 2 = CONST SP 15; 3 = LAST SPEED
603
30.3 EXTERNAL FAULT
1 = NOT SEL; 2 ... 7 = DI1 ... DI6
604
30.4 MOTOR THERM PROT
1 = FAULT; 2 = WARNING; 3 = NO
605
30.5 MOT THERM P MODE
1 = DTC; 2 = USER MODE; 3 = THERMISTOR
606
30.6 MOTOR THERM TIME
256 s ... 10 000 s
1 1 s
607
30.7 MOTOR LOAD CURVE
50 % ... 150 %
1 1 %
608
30.8 ZERO SPEED LOAD
25 % ... 150 %
609
30.9 BREAK POINT
1 Hz ... 300 Hz
30000 300 Hz
610
30.10 STALL FUNCTION
1 = FAULT; 2 = WARNING; 3 = NO
611
30.11 STALL FREQ HI
0.5 Hz ... 50 Hz
5000 50 Hz
612
30.12 STALL TIME
10 s ... 400 s
1 1 s
613
30.13 UNDERLOAD FUNC
1 = NO; 2 = WARNING; 3 = FAULT
614
30.14 UNDERLOAD TIME
0 s ... 600 s
1 1 s
615
30.15 UNDERLOAD CURVE
1; 2; 3; 4; 5
616
30.16 MOTOR PHASE LOSS
0 = NO; Hex FFFF = FAULT
617
30.17 EARTH FAULT
618
30.18 COMM FAULT FUNC
1 = FAULT; 2 = NO; 3 = CONST SP 15; 4 = LAST SPEED
619
30.19 COMM FAULT TIMEOUT
0.1 s ... 60 s
6000 60 s
31 AUTOMATIC RESET
626
31.1 NUMBER OF TRIALS
1; 2; 3; 4; 5
627
31.2 TRIAL TIME
1.0 s ... 180.0 s
18000 180 s
628
31.3 DELAY TIME
0.0 s ... 60.0 s
6000 60 s
629
31.4 OVERCURRENT
0 = NO; Hex FFFF = YES
630
31.5 OVERVOLTAGE
631
31.6 UNDERVOLTAGE
632
31.7 AI SIGNAL<MIN
PROFIBUS
Par. No.
(Add 4000 in
FMS Mode)
ACS 600 Parameter
Alternative Settings
Scaling
1 Hz
100
0.5 Hz
50
0.1 s
10
1 s
100
1 s
100