Appendix C – Technical Data
Installation and Start-up Guide for NPBA-01
C-3
NPBA-01
Enclosure: Plastic, dimensions 45 × 75 × 105 mm, Class IP 20
Mounting: Onto a standard mounting rail
Settings: Parameter Group 51 (set with the CDP 311 Control Panel)
Connectors:
•
Light transmitter (grey) and receiver (blue) for ACS 600
connection
One Combicon MVSTBW 2,5/8-ST-5,08 (8-pole, cross-section
2.5 mm
2
max.) screw terminal block for the fieldbus and power
supply:
General:
•
All materials are UL/CSA approved
•
Fast transient burst immunity: According to standard
IEC 801-4: 4 kV 5/50 ns
•
Noise emissions: According to standard EN 55022 B
X2
Description
1
D(P)
D(P) = Data Positive (Conductor 1 in twisted pair)
D(N) = Data Negative (Conductor 2 in twisted pair)
DG = Data Ground
2
D(N)
3
DG
4
SHF
Filtered Shield (Earthed via an RC filter)
5
SH
Shield (Earthed)
6
0V
Power supply for the module (3 W). From the NIOC card of the
ACS 600 (Terminal: X23.1 = +24 V, X23.2 = Earth/0 V) or from
another stable 24 V d.c. supply.
7
+24 V
8
PE
Earth