Appendix A – Parameter Listings
Installation and Start-up Guide for NPBA-01
A-5
14 RELAY OUTPUTS
201
14.1 RELAY RO1 OUTPUT
1 = NOT USED; 2 = READY; 3 = RUNNING; 4 = FAULT; 5 = FAULT(-1);
6 = FAULT(RST); 7 = STALL WARN; 8 = STALL FLT; 9 = MOT TEMP WRN;
10 = MOT TEMP FLT; 11 = ACS TEMP WRN; 12 = ACS TEMP FLT;
13 = FAULT/WARN; 14 = WARNING; 15 = REVERSED; 16 = EXT CTRL;
17 = REF 2 SEL; 18 = CONST SPEED; 19 = DC OVERVOLT;
20 = DC UNDERVOL; 21 = SPEED 1 LIM; 22 = SPEED 2 LIM;
23 = CURRENT LIM; 24 = REF 1 LIM; 25 = REF 2 LIM; 26 = TORQUE 1 LIM;
27 = TORQUE 2 LIM; 28 = STARTED; 29 = LOSS OF REF; 30 = AT SPEED;
31 = ACT 1 LIM; 32 = ACT 2 LIM
202
14.2 RELAY RO2 OUTPUT
203
14.3 RELAY RO3 OUTPUT
15 ANALOGUE OUTPUTS
226
15.1 ANALOGUE OUTPUT1
1 = NOT USED; 2 = P SPEED; 3 = SPEED; 4 = FREQUENCY; 5 = CURRENT;
6 = TORQUE; 7 = POWER; 8 = DC BUS VOLT; 9 = OUTPUT VOLT;
10 = APPL OUTPUT; 11 = REFERENCE; 12 = CONTROL DEV;
13 = ACTUAL 1; 14 = ACTUAL 2
227
15.2 INVERT AO1
0 = NO; Hex FFFF = YES
228
15.3 MINIMUM AO1
1 = 0 mA; 2 = 4 mA
229
15.4 FILTER AO1
0 s ... 10 s
1000 10 s
230
15.5 SCALE AO1
10 % ... 1000 %
10000
1000 %
231
15.6 ANALOGUE OUTPUT2
1 = NOT USED; 2 = P SPEED; 3 = SPEED; 4 = FREQUENCY; 5 = CURRENT;
6 = TORQUE; 7 = POWER; 8 = DC BUS VOLT; 9 = OUTPUT VOLT;
10 = APPL OUTPUT; 11 = REFERENCE; 12 = CONTROL DEV;
13 = ACTUAL 1; 14 = ACTUAL 2
232
15.7 INVERT AO2
0 = NO; Hex FFFF = YES
233
15.8 MINIMUM AO2
1 = 0 mA; 2 = 4 mA
234
15.9 FILTER AO2
0 s ... 10 s
1000 10 s
235
15.10 SCALE AO2
10 % ... 1000 %
10000
1000 %
16 SYSTEM CTR INPUTS
251
16.1 RUN ENABLE
1 = YES; 2 ... 7 = DI1 ... DI6; 8 = COMM.MODULE
252
16.2 PARAMETER LOCK
0 = OPEN; Hex FFFF = LOCKED
253
16.3 PASS CODE
0 ... 8 388 607
254
16.4 FAULT RESET SEL
1 = NOT SEL; 2 ... 7 = DI1 ... DI6; 8 = COMM.MODULE
255
16.5 USER MACRO IO CHG
1 = NOT SEL; 2 ... 7 = DI1 ... DI6
20 LIMITS
351
20.1 MINIMUM SPEED
-18000/(number of pole pairs) rpm ...
18000/(number of pole pairs) rpm
1 1 rpm
352
20.2 MAXIMUM SPEED
353
20.3 MAXIMUM CURRENT
0 %
I
hd
... 200 %
I
hd
20000 200 %
354
20.4 MAXIMUM TORQUE
0 % ... 300 %
1 1 %
355
20.5 OVERVOLTAGE CTRL
0 = OFF; Hex FFFF = ON
356
20.6 UNDERVOLTAGE CTRL
357
20.7 MINIMUM FREQ
- 300 Hz ... 300 Hz (effective only when the
SCALAR control mode is selected)
-30000 -300 Hz
358
20.8 MAXIMUM FREQ
PROFIBUS
Par. No.
(Add 4000 in
FMS Mode)
ACS 600 Parameter
Alternative Settings
Scaling
0
0 s
100
10 %
0
0 s
100
10 %
0
0 %
300 Hz
30000