Chapter 5 – Programming
5-7
Installation and Start-up Guide for NPBA-01
Analogue Outputs
The PROFIBUS master can read one actual signal from the drive at a
time. Two actual signals can be preset, and the selection between the
two signals is done with bit 11 of the Control Word (see Chapter 6,
Table 6-3). These parameters can only be set when the drive is
stopped.
15.1 ANALOGUE
OUTPUT1
This parameter selects Analogue output 1 of the ACS 600 and Actual
signal 1 available through the communication (fieldbus adapter)
module.
NOT USED, P SPEED, ..., CONTROL DEV
All the available alternatives are presented in Appendix A, Table A-1.
15.6 ANALOGUE
OUTPUT2
This parameter selects Analogue output 2 of the ACS 600 and Actual
signal 2 available through the communication (fieldbus adapter)
module.
NOT USED, P SPEED, ..., CONTROL DEV
All the available alternatives are presented in Appendix A, Table A-1.
System Control Inputs
The ACS 600 drive can receive the system control inputs from the
digital inputs and from the communication (fieldbus adapter) module.
16.1 RUN ENABLE
This parameter defines the source of the Run enable signal.
YES
The Run enable signal is set active. The ACS 600 is ready to start
without an external Run enable signal.
DI1,...,DI6
The Run enable signal is received through a digital input. See the
ACS
600 Programming Manual for more information.
COMM.MODULE
(Recommended Setting)
The Run enable signal is received through the communication (fieldbus
adapter) module.
16.4 FAULT RESET SEL
This parameter defines where faults are reset from.
(See also the
ACS 600 Programming Manual.)
NOT SEL
Fault reset is executed from the Control Panel.
DI1, ..., DI6
Fault reset is executed from an external switch or from the Control
Panel.
COMM.MODULE
(Recommended Setting)
Fault reset is executed via the communication (fieldbus adapter)
module or from the Control Panel.