KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
62
12.16.5
Extended parameter – Enable group object after return of voltage
Options
Blocked
Enable
Note: This object is only adjustable if the "Enable object" parameter is set to
"activated".
The parameter "Enable after return of voltage" exists to permit a defined behavior at the
"Enable" communication object after a return of bus voltage. A determination is made
here about whether a "1" ("enable") or a "0" ("blocked") is present on the enable object
after the return of bus voltage.
Note: If the logic of the enable function is set to "inverse", the behavior is also inverted
after the return of bus voltage, i.e. if the parameter "enable after return of bus voltage" is
set to "enable", and at the same time the "logic of the enable function" is parameterized
to "inverse", then the function will initially not be active after return of bus voltage. This
must first be activated via the receipt of an OFF telegram on the enable object.
12.16.6
Extended parameter –Send comfort object
Options
Deactivate
Activate
Only available when parameter "Object type for output" is set on "1 bit", and for operating
modes "Comfort", "Standby" and "ECO".
12.16.7
Extended parameter –Send ECO object
Options
Deactivate
Activate
Only available when parameter "Object type for output" is set on "1 bit" and for operating
modes "Standby", and "ECO".
12.16.8
Extended parameter – Send frost object
Options
Deactivate
Activate
Only available when parameter "Object type for output" is set on "1 bit", and for operating
modes "Comfort", "Standby" and "ECO".
12.16.9
Objects no
Object name
Data type
Flags
Application
activate/deactivate GO
1 bit DPT 1.001
C, W, U