KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
158
12.35.33
Slave – General – Setpoint display - Object no
Object name
Data type
Flags
Setpoint display – (master)
2 byte DPT 9.001
C, R, T
Setpoint display – (slave)
2 byte DPT 9.001
C, W, T, U
This 2-byte communication object must be connected to the respective slave
communication object in order to synchronize the devices in the master/slave
configuration.
12.35.34
Slave – General – Request setpoint - Object no
Object name
Data type
Flags
Request setpoint – (master)
1 byte DPT 5.001
C, W, U
Request setpoint – (slave)
1 byte DPT 5.001
C, T
This 1-byte communication object must be connected to the respective slave
communication object in order to synchronize the devices in the master/slave
configuration.
12.35.35
Slave – General – Confirm setpoint - Object no
Object name
Data type
Flags
Confirm setpoint – (master)
1 byte DPT 5.001
C, R, T
Confirm setpoint – (slave)
1 byte DPT 5.001
C, W, T, U
This 1-byte communication object must be connected to the respective slave
communication object in order to synchronize the devices in the master/slave
configuration.
12.35.36
Slave – General – Heating / Cooling request - Object no
Object name
Data type
Flags
Heating / cooling request –
(master)
1 bit DPT 1.001
C, W, U
Heating / cooling request –
(slave)
1 bit DPT 1.001
C, T
This 1-bit communication object must be connected to the respective slave
communication object in order to synchronize the devices in the master/slave
configuration.
12.35.37
Slave – General – Request fan speed level manual - Object no
Object name
Data type
Flags
Request fan speed level
manual – (master)
1 bit DPT 1.001
C, W, U
Request fan speed level
manual – (slave)
1 bit DPT 1.001
C, T
This 1-bit communication object must be connected to the respective slave
communication object in order to synchronize the devices in the master/slave
configuration.