KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
132
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device".
The current setpoint value can be sent to the bus either cyclically and after a change, or
only after a change.
12.34.86
Setpoint setting – Cyclic sending of the current setpoint temperature (min)
Options
Time input from 5 to 240
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and only available when the "Send current setpoint" is
set on "Cyclic and during change".
This parameter is use to specified the amount of time that will elapse before the current
setpoint value is automatically transmitted onto the bus line.
12.34.87
Setpoint setting – Basic setpoint is
Options
Setpoint for cooling comfort
Setpoint for heating comfort
Mean value between heating comfort and cooling
comfort
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device"
This parameter is used to specified the reference for basic setpoint.
12.34.88
Changing set value – Maximum manual increase during heating mode (°C)
Options
Input from 0 to 9
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device", and the Control function parameter is set on “Heating”,
“Heating with additional stage”, "Heating and cooling" or "Heating and cooling with
additional stages".