KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
91
Via the "Actuator group A" parameter, you can specify whether the actuator group A is
sent out or not for a call of the scene 1. Select the "activated" setting if the actuator group
A is to trigger a telegram for call of the scene 1.
12.29.9
Object no
Object name
Data type
Flags
Number of light scene
1 byte DPT 18.001
C, W
Actuator group A..H
1 bit DPT 1.001
C, W, T, U
12.30
Application “Delay”
Telegrams can be received via the "Input" object using the "Delay" application. The
telegrams received are sent out on the "Output" object with a set delay time.
The object types for "Input" and "Output" can be collectively parameterized for different
applications.
12.30.1
Channel – Object type
Options
1 bit switching
1 bit move blinds / shutter up-down
1 bit stop up-down
1 byte 0..100%
1 byte 0..255
2 byte float
2 byte signed
2 byte unsigned
4 byte float
4 byte signed
4 byte unsigned
The object types for "Input" and "Output" can be collectively parameterized for the
different application cases. The following sizes can be selected.
–
1 bit
: switching functions (e.g. On/Off, enable/blocked, true/untrue)
–
1 bit
: move blinds / shutter up-down
–
1 bit
: stop up-down
–
1 byte 0 - 100%:
percentage values (0 = 0%, 255 = 100%)
–
1 byte 0 - 255
: arbitrary values from 0 to 255
–
2-byte float
: floating point value (physical values such as temperature or brightness) -
671088.64 to 671088.64
–
2-byte signed
: arbitrary values from -32768 to +32767
–
2-byte unsigned
: arbitrary values from 0 to 65,535
–
4-byte float
: floating point value (physical values) -4000000 to 4000000
–
4-byte signed:
arbitrary values from -2147483648 to 2147483647
–
4-byte unsigned
: arbitrary values from 0 to 4294967295
12.30.2
Channel – Delay time (hh:mm:ss:ms)
Options
Time input from 00:00:01:00 to 01:00:00:00