KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
137
12.34.100
Temperature reading – Weighting of external measurement 2 (%)
Options
Input from 0 to 100
Note: This parameter is only available when the "Device function" parameter is
set on either "Single device" or "Master device" and the "Inputs of weighted temperature
reading" parameter is set on "2 x external measurement" or "Internal and 2x external
measurement".
Specifies the weighting of the external measurement 2 at a level between 0% and 100%.
When added together with the (0%...100%) weighting of the external measurement, the
result must be 100%.
12.34.101
Temperature reading – Cyclic sending of the actual temperature (min)
Options
Input from 5 to 240
Note: This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
The current actual temperature used by the device can be cyclically transmit onto the bus
line.
12.34.102
Temperature reading – Difference of value for sending the actual
temperature (x 0.1 °C)
Options
Input from 1 to 100
Note: This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
If the change in temperature exceeds the parameterized difference between the
measured actual temperature and the previous actual temperature that was sent, the
changed value will be transmitted.