Communication objects
Communication objects
Product manual 2CKA001473B9679
│357
12.1.70 RTC - Fan speed level x (cooling)
Name
Object function
Data type
RTC: Fan speed level x (cooling)
Output
1.001 Switching
These, up to five communication objects send the current fan speed level of the second fan coil
actuator (cooling) via 1-bit switching commands to the actuator.
If a fain coil regulator is set for both operating modes of heating and cooling and an own
generating device is set for both operating modes, this communication object then operates
jointly with fan coil regulator cooling.
12.1.71 RTC - Current HVAC operating mode
Name
Object function
Data type
RTC: Current HVAC operating
mode
Output
20.102 HVAC mode
The RTC uses this communication object to send the operating mode that belongs to the
currently set setpoint temperature.
RTC operating mode
Current HVAC operating mode
Error
Building protection
Comfort override operating mode
Comfort
Standby override operating mode
Standby
Economy: Override operating mode
Economy
Building protection override operating mode
Building protection
Condensate water alarm
Building protection
Dew point alarm
Building protection
Window open
Building protection
Control OFF
Building protection
Presence
Comfort
Comfort
Comfort
Standby
Standby
Economy
Economy
Building protection
Building protection
Table 8: Operating mode
Содержание ClimaECO SB/Ux.0.1 Series