Description of application and parameters
"Relative humidity" application
Product manual 2CKA001473B9679
│205
11.6.64 Dew point alarm — Switch command at the end of the dew point alarm
Options:
Off
On
If the dew point alarm is no longer present at the object, this parameter can be used to define
which status should be sent.
11.6.65 Dew point alarm — Priority for dew point alarm
Options:
End priority
OFF with priority
ON with priority
The parameter defines which state should be sent in case of a dew point alarm.
11.6.66 Dew point alarm — Priority at the end of the dew point alarm
Options:
End priority
OFF with priority
ON with priority
If the dew point alarm is no longer present at the object, this parameter can be used to define
which status should be sent.
11.6.67 Dew point alarm — Percent for dew point alarm
Options:
0-100%
This parameter defines which value between 0 and 100% is sent in case of a dew point alarm.
11.6.68 Dew point alarm — Percent at the end of the dew point alarm
Options:
0-100%
If the dew point alarm is no longer present at the object, this parameter can be used to define
which value between 0 and 100% should be sent.
11.6.69 Dew point alarm — Value for dew point alarm (0 - 255)
Options:
0-255
This parameter defines which value between 0 and 255 is sent in case of a dew point alarm.
11.6.70 Dew point alarm — Value at the end of the dew point alarm (0 - 255)
Options:
0-255