Communication objects
Communication objects
Product manual 2CKA001473B9679
│341
12.1.26 RTC - Superimposed operating mode
Name
Object function
Data type
RTC: Override operating mode
Input
20.102 HVAC mode
RTC: Override operating mode
(Master/Slave)
Input
20.102 HVAC mode
The value for the switchover of the operating mode is received via the 1-byte communication
object. Meaning of values:
■
"0": Override operating mode inactive
■
"1": Comfort
■
"2": Standby
■
"3": Economy
■
"4": Building protection
In addition to manual setpoint adjustment and the adjustment of the basic setpoint value, the
setpoint temperature of the controller is defined by the following communication objects: (listed
in decreasing order of priority).
■
"
RTC: Override operating mode"
■
"RTC: Condensate water alarm"
■
"RTC: Dew point alarm"
■
"
RTC: Window contact"
■
"
RTC: Control On/Off"
■
"
RTC: Presence detector"
■
"
RTC: Normal operating mode"
Notice
When the master/slave operation is activated, the object "RTC: Override
operating mode (master/slave)" of the master and slave device must be
connected with the group address of the sending device.