Communication objects
Communication objects
Product manual 2CKA001473B9679
│337
12.1.15 RTC — Status control value of basic heating stage
Name
Object function
Data type
RTC: Status control value of basic heating
stage
Output
1.001 Switching
5.001 Percent (0..100%)
– The 1-bit communication object is used to operate a switching actuating drive, e.g. a
thermoelectric actuating drive, that is controlled by a switching/heating actuator.
– The 1-byte communication object is used to control an actuating drive with a continuous
input value (0%..100%), e.g. an electromotive actuating drive.
12.1.16 RTC — Status control value of additional heating stage
Name
Object function
Data type
RTC: Status control value of additional
heating stage
Output
1.001 Switching
5.001 Percent (0..100%)
– The 1-bit communication object is used to operate a switching actuating drive, e.g. a
thermoelectric actuating drive, that is controlled by a switching/heating actuator.
– The 1-byte communication object is used to control an actuating drive with a continuous
input value (0%..100%), e.g. an electromotive actuating drive.
Notice
The additional stage can also be used as a parallel second heating stage. To do
this, the parameter for the temperature difference to the basic stage must be set
on 0°C.
12.1.17 RTC — Status control value of basic cooling stage
Name
Object function
Data type
RTC: Status control value of basic cooling
stage
Output
1.001 Switching
5.001 Percent (0..100%)
– The 1-bit communication object is used to operate a switching actuating drive, e.g. a cooling
ceiling, that is controlled by a switching/heating actuator.
– The 1-byte communication object is used to control an actuating drive with a continuous
input value (0%..100%), e.g. an electromotive actuating drive.