Description of application and parameters
Application "Device settings"
Product manual 2CKA001473B9679
│80
■
Off:
– If a telegram with value "1" is received via the object "DS: Display day/night", the display
does not light up.
■
50 %:
– If a telegram with value "1" is received via the object "DS: Display day/night", the display
lights up 50% white.
■
100 %:
– If a telegram with value "1" is received via the object "DS: Display day/night", the display
lights up 100% white.
Notice
The parameter is adjustable only when parameter "Display backlighting white" is
set on "via communication object day/night" or "via communication object
day/night and RTC operation".
11.1.4.16
Display backlighting red
Options:
No
CO
2
value
Humidity value
CO
2
and humidity value
Via communication object
■
No:
– The device displays white only.
■
CO2 value:
– When exceeding the set CO2 value, the device changes into red display backlighting, if
parameterized.
■
Humidity value:
– When exceeding the highest set step of the humidity value, the device changes into red
display backlighting, if parameterized.
■
CO2 and humidity value:
– When exceeding the highest set step of the CO2 and humidity value, the device
changes into red display backlighting, if parameterized.
■
Via communication object:
– If a telegram with value "1" is received via object "DS: Display backlighting red", the
display changes into red display backlighting, if parameterized.
Содержание ClimaECO SB/Ux.0.1 Series
Страница 382: ...Notes Product manual 2CKA001473B9679 382 13 Notes ...