Description of application and parameters
Application "Function block x"
Product manual 2CKA001473B9679
│237
11.7.9.2
Reaction on rising edge
Options:
No reaction
Value 1
Value 2
Alternating value1/value2
■
No reaction:
– No telegram is sent at the press of the button.
■
Value 1:
– Value 1 is sent at the press of the button (at rising edge).
■
Value 2:
– Value 2 is sent at the press of the button (at rising edge).
■
Alternating value 1/value 2:
– Value 1 and value 2 are sent alternately at the press of the button.
Application "1-button value transmitter" can differentiate between the press and the releasing of
the button. A press is defined as "Rising edge" and the releasing as "Falling edge". Only one
communication object is available for both edges.
The parameter is used to specify whether a telegram with value 1 or value 2 is sent on the bus
at a rising edge via communication object "Sx: switching". A further option can be specified as to
whether the telegrams are sent alternately. This means that after value 1 has been sent, value 2
is sent at a renewed press of the button. After it is pressed again, value 1 is again sent out.
Note
Parameter "Value 1" and "Value 2" is used to specify the values that are to be
sent.