Description of application and parameters
Application "RTC"
Product manual 2CKA001473B9679
│124
11.4.1 Setpoint settings - Setpoint adjustment via communication object (DPT 9.001)
Options:
No
For comfort, Eco, standby
For comfort, Eco, standby, building protection
The communication objects that allow the adjustment of the parameterised setpoints via the bus
are enabled via the associated parameters.
Notice
If the received temperature values are not possible (heating setpoint via cooling
setpoint or on the other side the comfort or building protection values), they are
then ignored. To display this event a telegram with value "1" is sent via
communication object "Setpoint error".
11.4.1 Setpoint settings - Hide temperature unit
Options:
No
Yes
This parameter makes it possible to hide the temperature unit as well as the absolute and the
relative setpoint. This standardises the function between master/individual device and slave
devices.
11.4.2 Setpoint settings — Display indicates
Options:
Current setpoint
Relative setpoint
The display can indicate either the absolute or relative setpoint value.
–
Current setpoint
: On devices with a display, the setpoint is shown as an absolute
temperature, e.g. 21.0°C.
–
Relative setpoint
: On devices with display, the setpoint is indicated as a relative value, e.g. -
5°C .. + 5°C.
11.4.3 Setpoint settings — Send current setpoint
Options:
Cyclic and during change
Only for change
The current setpoint value can be sent to the bus either cyclically and after a change, or only
after a change.
11.4.4 Setpoint settings — Cyclic sending of the current set-point temperature (min)
Options:
Setting option between 5 - 240