12.1.66 RTC - Limit temperature additional cooling stage
Name
Object function
Data type
RTC: Limit temperature additional cooling
stage
Input
9.001 Temperature value
The communication object receives the measured temperature value for the limit temperature of
the additional cooling stage. The function is analogue to the heating limit temperature.
12.1.67 RTC — Confirm fan (cooling) manually
Name
Object function
Data type
RTC; Confirm fan (cooling) manually
Output
1.001 Switching
The communication object signals the status of the second fan output (cooling)
manually/automatic to the bus. Manual mode is signalled with value 1, automatic mode with
value 0.
12.1.68 RTC - Fan speed level (cooling)
Name
Object function
Data type
RTC: Fan speed level (cooling)
Output
5.001 Percentage value
6.010 Counter value
The fan speed level to be set is sent to the second fan coil actuator (cooling) via the
communication object. The parameter can be used to set whether the fan speed level is sent
only in manual or also in automatic mode. A counter value or a percentage value can be set as
data format.
If a fain coil regulator is set for both operating modes of heating and cooling and an own
generating device is set for both operating modes, this communication object then operates
jointly with fan coil regulator cooling.
12.1.69 RTC - Fan speed level status (cooling)
Name
Object function
Data type
RTC: Fan speed level status
(cooling)
Input
5.001 Percentage value
6.010 Counter value
The communication object receives the current fan speed level of the second fan coil actuaor
(cooling). This the RTC uses for the display of the fan speed level and as starting point for its
adjustment. The speed level in the RTC is determined as standard from the current control
value or the manual adjustment.
If a fain coil regulator is set for both operating modes of heating and cooling and an own
generating device is set for both operating modes, this communication object then operates
jointly with fan coil regulator cooling.