11.4.1 Temperature limiter - Temperature limit of heating - Integral component of the PI
controller
Options:
Keep
Reset
The parameter is used to define the processing of the I-component of a PI controller for
temperature limiting.
If the I-component is retained, this value is the starting point for continuing the PI controller after
the termination of the temperature limit. This option is suitable for slow control systems.
If the I-component is reset, the PI controller starts after the termination of the temperature limit
with an I-component of zero. This option is suitable for fast control systems.
If no PI controller is used, this parameter is without function.