Communication objects
Communication objects
Product manual 2CKA001473B9679
│339
12.1.21 RTC - External actual temperature
Name
Object function
Data type
RTC: External actual temperature
Input
9.001 Temperature value
The temperature value of an external temperature sensor is received via the 2-byte
communication object.
Notice
An external temperature measurement for room temperature control may be
practical for larger rooms and/or floor heating.
12.1.22 RTC - External actual temperature 2
Name
Object function
Data type
RTC: External actual temperature
2
Input
9.001 Temperature value
The temperature value of a second external temperature sensor is received via the 2-byte
communication object.
Notice
An external temperature measurement for room temperature control may be
practical for larger rooms and/or floor heating.
12.1.23 RTC - Fault of actual temperature
Name
Object function
Data type
RTC: Fault of actual temperature
Output
1.001 Switching
RTC: Fault of actual temperature
(Master)
Output
1.001 Switching
RTC: Fault of actual temperature
(Slave)
Output
1.001 Switching
If one of the parameterised input temperatures is unavailable to the controller for a period longer
than the monitoring time, the controller enters the error mode. The device sends a telegram on
the bus with value"1".
Notice
When the master/slave operation is activated, the object "RTC: Fault of actual
temperature (master)" of the master device must be connected with object "RTC:
Fault of actual temperature (slave)" of the slave device to display the faulty
operation.