Description of application and parameters
Application "RTC"
Product manual 2CKA001473B9679
│119
11.4.72 Setpoint settings
Note
This parameter is only available if the "Device function" parameter is set on
either "Single device" or "Master device".
11.4.73 Setpoint settings — Setpoint for heating comfort = setpoint for cooling comfort
Options:
No
Yes
This parameter is used to configure the manner in which the setpoint adjustment functions.
–
Yes
: The device has the same setpoint for heating and cooling in the comfort mode. The
system switches to heating when the temperature drops below the setpoint minus
hysteresis. It switches to cooling when the temperature exceeds the setpoint plus
hysteresis. The hysteresis is parameterizable.
–
No
: The function has two separate setpoints for heating and cooling in the comfort mode.
The device will display the currently active setpoint value. Switching between heating and
cooling occurs via the "Switchover heating/cooling" parameter setting.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
11.4.1 Setpoint settings — Standby and Eco are absolute values
Options:
No
Yes
This parameter is used to set the indication of the display for standby and Eco mode.
■
Yes:
– The setpoints for standby and Eco mode are entered as absolute values.
■
No:
– The setpoints for standby and Eco mode are entered as temperature difference to the
setpoint of comfort mode. At an adjustment of the comfort setpoint temperature during
operation of the device the setpoints for standby and Eco mode are shifted at the same
temperature difference from comfort mode.