12-78 Startup Assistant & Parameters
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
EMBEDDED
FIELDBUS
(Continued)
COMMUNICATION
CONTROL
(58.06)
Default: 0 (Enabled)
Range: 0 - 2
0 (Enabled)
Normal operation
1 (Refresh settings) Validates any changed EFB configuration settings. Reverts
automatically to Enabled.
2 (Silent mode)
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the Refresh settings
selection of this parameter.
Validates any changes in the EFB settings, or activates silent mode.
COMMUNICATION
DIAGNOSTICS
(58.07)
Default:
Read Only
Range: 0000h - FFFFh
Displays the status of the EFB communication.
This parameter is read-only.
Bit
Name
Information
0
Init failed
1 = EFB initialization failed
1
Addr config err
1 = Node address not allowed by protocol
2
Silent mode
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
3
Autobauding
Reserved
4
Wiring error
1 = Errors detected (A/B wires possibly
swapped)
5
Parity error
1 = Error detected: check parameters
58.04 and 58.05
6
Baud rate error
1 = Error detected: check parameters
58.05 and 58.04
7
No bus activity
1 = 0 bytes received during last 5 seconds
8
No packets
1 = 0 packets (addressed to any device)
detected during last 5 seconds
9
Noise or
addressing error
1 = Errors detected (interference, or
another device with the same address on
line)
10
Comm loss
1 = 0 packets addressed to the drive
received within timeout (58.16)
11
CW/Ref loss
1 = No control word or references received
within timeout (58.16)
12
Not active
Reserved
13
Protocol 1
Reserved
14
Protocol 2
Reserved
15
Internal error
Reserved
RECEIVED PACKETS
(58.08)
Default: -
Range: 0 - 4294967295
Displays a count of valid packets addressed to the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...