12-50 Startup Assistant & Parameters
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
STANDARD DIO,
FI, FO
(Continued)
DIO DELAYED STATUS
(11.02)
Default:
Read Only
Range: 0000b - 0011b
Displays the delayed status of digital input/outputs DIO2 and DIO1.
This word is updated only after activation/deactivation delays (if any
are specified). Example: 0010 = DIO2 is on, DIO1 is off.
This parameter is read-only.
DIO1 FUNCTION
(11.05)
Default: Output (0)
Range: 0 - 2
Output (0) DIO1 is used as a digital output
Input (1) DIO1 is used as a digital input
Frequency (2) DIO1 is used as a frequency input
Selects whether DIO1 is used as a digital output or input, or a
frequency input.
DIO1 OUTPUT SOURCE
(11.06) Default: Ready run (2)
Range: 0 - 44, Other
Not energized (0) Output is off
Energized (1) Output is on
Ready run (2) Bit 1 of 06.11 Main status word
Enabled (4) Bit 0 of 06.16 Drive status word 1
Started (5) Bit 5 of 06.16 Drive status word 1
Magnetized (6) Bit 1 of 06.17 Drive status word 2
Running (7) Bit 6 of 06.16 Drive status word 1
Ready ref (8) Bit 2 of 06.11 Main status word
At setpoint (9) Bit 8 of 06.11 Main status word
Reverse (10) Bit 2 of 06.19 Speed control status word
Zero speed (11) Bit 0 of 06.19 Speed control status word
Above limit (12) Bit 10 of 06.17 Drive status word 2
Warning (13) Bit 7 of 06.11 Main status word
Fault (14) Bit 3 of 06.11 Main status word
Fault (-1) (15) Inverted bit 3 of 06.11 Main status word
Open brake command (22) Bit 0 of 44.01 Brake control status
Ext2 active (23) Bit 11 of 06.16 Drive status word 1
Remote control (24) Bit 9 of 06.11 Main status word
Supervision 1 (33) Bit 0 of 32.01 Supervision status
Supervision 2 (34) Bit 1 of 32.01 Supervision status
Supervision 3 (35) Bit 2 of 32.01 Supervision status
RO/DIO control word bit 0 (40) Bit 0 of 10.99 RO/DIO control word
RO/DIO control word bit 1 (41) Bit 1 of 10.99 RO/DIO control word
RO/DIO control word bit 2 (42) Bit 2 of 10.99 RO/DIO control word
RO/DIO control word bit 8 (43) Bit 8 of 10.99 RO/DIO control word
RO/DIO control word bit 9 (44) Bit 9 of 10.99 RO/DIO control word
Other [bit] Source selection (see Terms and abbreviations)
Selects a drive signal to be connected to digital input/output DIO1
when parameter 11.05 DIO1 function is set to Output.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...