Startup Assistant & Parameters 12-89
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
HW
CONFIGURATION
CONTROL BOARD SUPPLY
(95.04)
Default: 0 (Internal 24V)
Range: 0 - 2
0 (Internal 24V) The drive control unit is powered from the drive power unit it is
connected to.
1 (External 24V) The drive control unit is powered from an external power supply.
2 (Redundant external 24V) (Type BCU control units only) The drive control unit is powered from
two redundant external power supplies. The loss of one of the supplies
generates a warning (AFEC External power signal missing).
Specifies how the control unit of the drive is powered.
SYSTEM
LANGUAGE
(96.01)
Default: English
Range: -
Not selected None
English English
Deutsch German
Italiano Italian
Español Spanish
Portugues Portuguese
Nederlands Dutch
Français French
Dansk Danish
Suomi Finnish
Svenska Swedish
Russki Russian
Polski Polish
Czech Czech
Türkçe Turkish
Selects the language of the parameter interface and other displayed
information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the Drive
composer PC tool. (Those are specified under View – Settings.)
PASS CODE
(96.02)
Default: -
Range: 0 to 99999999
14 CTDD User
13 Fieldbus
12 Expert Commissioner
Does not default. Setting access level to 13 (Fieldbus) opens all Fieldbus
applicable parameters (groups 50 to 56 and monitoring parameters 3.05,
3.06, 6.01 and 6.11). Expert commissioner enables all parameters in the
drive by setting 96.02 = 12.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...