12-68 Startup Assistant & Parameters
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
LIMITS
(Continued)
TORQUE LIMIT STATUS
(30.02)
Default:
Read Only
Range: 0000h - FFFFh
Displays the torque controller limitation status word.
This parameter is read-only.
Bit
Name
Information
0
Undervoltage
*1 = Intermediate DC circuit undervoltage
1
Overvoltage
*1 = Intermediate DC circuit overvoltage
2
Minimum torque
*1 = Torque is being limited by 30.26
Power motoring limit, 30.27 Power
generating limit or the source of 30.18
Minimum torque sel.
3
Maximum torque
*1 = Torque is being limited by 30.26
Power motoring limit, 30.27 Power
generating limit or the source of 30.25
Maximum torque sel.
4
Internal current
1 = An inverter current limit (identified by
bits 8 - 11) is active
5
Load angle
(With permanent magnet motors and
synchronous reluctance motors only)
1 = Load angle limit is active, ie. the motor
cannot produce any more torque
6
Motor pullout
(With asynchronous motors only)
1 = Motor pull-out limit is active, ie. the
motor cannot produce any more torque
7
Reserved
8
Thermal
1 = Input current is being limited by the
main circuit thermal limit
9
Max current
*1 = Maximum output current (
I
MAX
) is being
limited
10
User current
*1 = Output current is being limited by
30.17 Maximum current
11
Thermal IGBT
*1 = Output current is being limited by a
calculated thermal current value
12
IGBT
overtemperature
*1 = Output current is being limited
because of estimated IGBT temperature
13
IGBT overload
*1 = Output current is being limited
because of IGBT junction to case
temperature
14-15
Reserved
*Only one out of bits 0 - 3, and one out of bits 9 - 13 can be on simultaneously.
The bit typically indicates the limit that is exceeded first.
MAXIMUM SPEED
(30.12)
Default: 0.00 RPM
Range: -30000.00 to +30000.00 RPM
Defines the maximum allowed speed. Value is adjustable from 99.09
motor nominal speed or lower.
WARNING:
This value must not be lower than 30.11 Minimum speed.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...