Startup Assistant & Parameters 12-43
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
SYSTEM INFO
(Continued)
APPLICATION NAME
(07.23)
Default:
Read Only
Range: –
First five ASCII letters of the name given to the application program in
the programming tool. The full name is visible under System info on
the control panel or the Drive composer PC tool.
_N/A_ = None
APPLICATION VERSION
(07.24) Default:
Read Only
Range: –
Application program version number given to the application program
in the programming tool. Also visible under System info on the control
panel or the Drive composer PC tool.
CUSTOMIZATION PACKAGE
NAME
(07.25)
Default:
Read Only
Range: –
First five ASCII letters of the name given to the customization package.
The full name is visible under System info on the control panel or the
Drive composer PC tool.
_N/A_ = None
CUSTOMIZATION PACKAGE
NAME
(07.26)
Default:
Read Only
Range: –
Customization package version number. Also visible under System info
on the control panel or the Drive composer PC tool.
ADAPTIVE PROGRAM STATUS
(07.30)
Default:
Read Only
Range: 0000h - FFFFh
Shows the status of the adaptive program. See section Adaptive
programming.
Bit
Name
Description
0
Initialized
1 = Adaptive program initialized
1
Editing
1 = Adaptive program is being edited
2
Edit done
1 = Editing of adaptive program finished
3
Running
1 = Adaptive program running
4-13
Reserved
14
State changing
1 = State change in progress in adaptive
programming engine
15
Faulted
1 = Error in adaptive program
STANDARD DI, RO
Configuration of digital inputs and relay outputs.
DI STATUS
(10.01)
Default:
Read Only
Range: 0000h - FFFFh
Displays the electrical status of digital inputs DIIL and DI6 - DI1. The
activation/deactivation delays of the inputs (if any are specified) are
ignored. A filtering time can be defined by parameter 10.51 DI filter
time.
Bits 0 - 5 reflect the status of DI1 - DI6; bit 15 reflects the status of the
DIIL input. Example: 1000000000010011b = DIIL, DI5, DI2 and DI1 are
on, DI3, DI4 and DI6 are off.
This parameter is read-only.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...