Startup Assistant & Parameters 12-93
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
MOTOR DATA
(Continued)
MOTOR NOMINAL SPEED
(99.09)
Default: 0 RPM
Range: 0 - 650 RPM
Defines the nominal motor speed. The setting must match the value on
the rating plate of the motor.
Note:
This parameter cannot be changed while the drive is running.
MOTOR NOMINAL POWER
(99.10)
Default: 0.00 kW or hp
Range: -10000.00 to +10000.00 kW or -13404.83 to +13404.83 hp
Defines the nominal motor power. The setting must match the value on
the rating plate of the motor. The unit is selected by parameter 96.16 Unit
selection.
Note:
This parameter cannot be changed while the drive is running.
ID RUN REQUESTED
(99.13)
Default: 0 (None)
Range: 0 - 6
0 (None) See Firmware Manual.
1 (Normal) See Firmware Manual.
2 (Reduced) See Firmware Manual.
3 (Standstill)
Preferred ID run mode for cooling tower applications -- Standstill
ID run. The motor is injected with DC current. With an AC induction
(asynchronous) motor, the motor shaft is not rotated. With a permanent
magnet motor, the shaft can rotate up to half a revolution.
4 (Autophasing) See Firmware Manual.
5 (Current Measurement
Calibration) See Firmware Manual.
6 (Advanced) See Firmware Manual.
7 (Advanced Standstill) See Firmware Manual.
Selects the type of the motor identification routine (ID run) performed
at the next start of the drive. During the ID run, the drive will identify the
characteristics of the motor for optimum motor control.
If no ID run has been performed yet (or if default parameter values have
been restored using parameter 96.06 Parameter restore), this parameter is
automatically set to Standstill, signifying that an ID run must be
performed. After the ID run, the drive stops and this parameter is
automatically set to None.
Notes:
•
For the Advanced ID run, the machinery must always be de-coupled
from the motor.
•
With a permanent magnet or synchronous reluctance motor, a
Normal, Reduced or Standstill ID run requires that the motor shaft is
NOT locked and the load torque is less than 10%.
•
With scalar control mode (99.04 Motor control mode = Scalar), only
the Current measurement calibration ID run mode is possible.
•
Once the ID run is activated, it can be canceled by stopping the drive.
•
The ID run must be performed every time any of the motor
parameters (99.04, 99.06 - 99.12) have been changed.
•
Ensure that the Safe torque off and emergency stop circuits (if any)
are closed during the ID run.
•
Mechanical brake (if present) is not opened by the logic for the ID run.
•
This parameter cannot be changed while the drive is running.
LAST ID RUN PERFORMED
(99.14)
Default: 0 (None)
Range: 0 - 6
Shows the type of ID run that was performed last.
• See parameter 99.13.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...