Startup Assistant & Parameters 12-77
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
FIELDBUS
ADAPTER
Parameters 50 - 56 are for FIELDBUS ONLY and are adapter module-specific. For more
information, see the documentation of the fieldbus adapter module. Note that not all of these
parameters are necessarily in use.
EMBEDDED
FIELDBUS
Configuration of the embedded fieldbus (EFB) interface. See also chapter Fieldbus control through the
embedded fieldbus interface (EFB).
PROTOCOL ENABLE
(58.01)
Default: 0 (None)
Range: 0, 1
0 (None)
None (communication disabled)
1 (Modbus RTU) Embedded fieldbus interface is enabled and uses the Modbus RTU
protocol
Enables/disables the embedded fieldbus interface and selects the
protocol to use.
Note:
When the embedded fieldbus interface is enabled, the drive-to-
drive link functionality is automatically disabled.
PROTOCOL ID
(58.02)
Default:
Read Only
Range: -
Displays the protocol ID and revision.
This parameter is read-only.
NODE ADDRESS
(58.03)
Default: 1
Range: 0 - 255
Defines the node address of the drive on the fieldbus link.
Values 1 - 247 are allowable. Two devices with the same address are
not allowed on-line.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
BAUD ADDRESS
(58.04)
Default: 3 (19.2 kbps)
Range: 2 - 7
2 (9.6 kbps)
9.6 kbit/s
3 (19.2 kbps) 19.2 kbit/s
4 (38.4 kbps) 38.4 kbit/s
5 (57.6 kbps) 57.6 kbit/s
6 (76.8 kbps) 76.8 kbit/s
7 (115.2 kbps) 115.2 kbit/s
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
PARITY
(58.05)
Default: 2 (8 EVEN 1)
Range: 0 - 3
0 (8 NONE 1)
Eight data bits, no parity bit, one stop bit
1 (8 NONE 2) Eight data bits, no parity bit, two stop bits
2 (8 EVEN 1) Eight data bits, even parity bit, one stop bit
3 (8 ODD 1) Eight data bits, odd parity bit, one stop bit
Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...