Technical Specifications A-5
3AXD50000011888
Efficiency
Approximately 98% at nominal power level
Protection Classes
Degree of
Protection
(IEC/EN 60529)
IP21, IP55
Enclosure Types
(UL508C)
UL Type 1, UL Type 12. For indoor use only
Overvoltage
Category
(IEC 60664-1)
III
Protective Class
(IEC/EN 61800-5-1)
I
Ambient Conditions
Environmental limits for the drive are given below. The drive is to be used in a heated, indoor, controlled
environment.
Operation Installed for
Stationary Use
Storage in the
Protective Package
Transportation in the
Protective Package
Installation Site Altitude
1. 0 to 4000m (13123 ft)
above sea level
2. 0 to 2000m (6561 ft)
above sea level
Above 1000m [3281 ft]
-
-
1. For neutral-grounded TN and TT systems and non-corner grounded IT
systems
2. For corner-grounded TN, TT and IT systems
Air Temperature
-15 to +55°C (5 to 131°F).
No frost allowed. See
Chapter 3 Ratings.
-40 to +70°C
(-40 to +158°F)
-40 to +70°C
(-40 to +158°F)
Relative Humidity
5 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
Contamination Levels
(IEC 60721-3-3, IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
Chemical gases:
Class 3C2
Solid particles:
Class 3S2
Chemical gases:
Class 1C2
Solid particles:
Class 1S3
Chemical gases:
Class 2C2
Solid particles:
Class 2S2
Atmospheric Pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration (IEC 60068-2)
Max. 1mm
(0.04in.)
(5 to 13.2 Hz),
max. 7m/s
2
(23ft/s
2
)
(13.2 to 100 Hz)
sinusoidal
Max. 1mm
(0.04in.)
(5 to 13.2 Hz),
max. 7m/s
2
(23ft/s
2
)
(13.2 to 100 Hz)
sinusoidal
Max. 3.5mm
(0.14in.)
(2 to 9 Hz),
max. 15m/s
2
(49ft/s
2
)
(9 to 200 Hz)
sinusoidal
Shock (IEC 60068-2-27)
Not allowed
Max. 100m/s2
(330 ft./s
2
), 11ms
Max. 100m/s
2
(330 ft./s2), 11ms
Free Fall
Not allowed
100mm (4 in.) for weight
over 100 kg (220 lb)
100mm (4 in.) for weight
over 100 kg (220 lb)
Table A-1 N5350 Technical Data Continued
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...