Startup Assistant & Parameters 12-25
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
WARNINGS
AND FAULTS
(Continued)
EVENT WORD 1 BIT 15
CODE
(04.71)
Default: 0000h
Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 15 of 04.40 Event
word 1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 15 AUX
CODE
(04.72)
Default: 0000 0000h
Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
DIAGNOSTICS
Various run-time-type counters and measurements related to drive maintenance. All parameters in this
group are read-only unless otherwise noted.
ON-TIME COUNTER
(05.01)
Default:
Read Only
Range: 0 - 65535 d
On-time counter - The counter runs when the drive is powered.
RUN-TIME COUNTER
(05.02)
Default:
Read Only
Range: 0 - 65535 d
Motor run-time counter - The counter runs when the inverter
modulates.
FAN ON-TIME COUNTER
(05.04)
Default:
Read Only
Range: 0 - 65535 d
Cooling fan run-time counter - Running time of the drive cooling fan.
Can be reset from the control panel by keeping Reset depressed for
over 3 sec.
INVERTER TEMPERATURE
(05.11)
Default:
Read Only
Range: -40.0 to +160.0 %
Drive temperature in percent - Estimated drive temperature in percent
of fault limit. The fault limit varies according to the type of the drive.
0.0% = 0°C (32°F); 100.0% = Fault limit
DIAGNOSTIC WORD 3
(05.22) Default:
Read Only
Range: 0000h - FFFFh
Diagnostic word 3.
Bit
Name
Value
0 - 10
Reserved
11
Fan command 1 = Drive fan is rotating above idle speed.
12 - 15
Reserved
MAIN FAN SERVICE
COUNTER
(05.41)
Default:
Read Only
Range: 0 to 150%
Main cooling fan age. Displays the age of the main cooling fan as a
percentage of its estimated lifetime. The estimate is based on the duty,
operating conditions and other operating parameters of the fan. When
the counter reaches 100%, a warning (A8C0 Fan service counter) is
generated.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...