12-26 Startup Assistant & Parameters
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
DIAGNOSTICS
(Continued)
AUX. FAN SERVICE
COUNTER
(05.42)
Default:
Read Only
Range: 0 to 150%
Auxiliary cooling fan age. Displays the age of the auxiliary cooling fan
as a percentage of its estimated lifetime. The estimate is based on
the duty, operating conditions and other operating parameters of the
fan. When the counter reaches 100%, a warning (A8C0 Fan service
counter) is generated.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
CONTROL AND
STATUS WORDS
All parameters in this group are read-only unless otherwise noted.
These parameters are for Fieldbus only. Main Control Word only used in “Custom” mode.
MAIN CONTROL WORD
(06.01)
Default:
Read Only
Range: 0 - 15
0 (Off1 control)
1 - Proceed to READY TO OPERATE.
0 - Stop along currently active deceleration ramp. Proceed to OFF1
ACTIVE; proceed to READY TO SWITCH ON unless other
interlocks (OFF2, OFF3) are active.
1 (Off2 control)
1 - Continue operation (OFF2 inactive).
0 - Emergency OFF, coast to a stop.
Proceed to OFF2 ACTIVE, proceed to SWITCH-ON INHIBITED.
2 (Off3 control)
1 - Continue operation (OFF3 inactive).
0 - Emergency stop, stop within time defined by drive parameter.
Proceed to OFF3 ACTIVE; proceed to SWITCH-ON INHIBITED.
3 (Run)
1 - Proceed to OPERATION ENABLED.
Note: Run enable signal must be active; see drive documentation.
If the drive is set to receive the Run enable signal from the
fieldbus, this bit activates the signal.
0 - Inhibit operation. Proceed to OPERATION INHIBITED.
4 (Ramp out zero)
1 - Normal operation. Proceed to RAMP FUNCTION GENERATOR:
OUTPUT ENABLED.
0 - Force Ramp function generator output to zero. The drive will
immediately decelerate to zero speed (observing the torque limits).
5 (Ramp hold)
1 - Enable ramp function. Proceed to RAMP FUNCTION GENERATOR:
ACCELERATOR ENABLED.
0 - Halt ramping (Ramp Function Generator output held).
6 (Ramp in zero)
1 - Normal operation. Proceed to OPERATING.
Note: This bit is effective only if the fieldbus interface is set as the
source for this signal by drive parameters.
0 - Force Ramp function generator input to zero.
7 (Reset)
0=>1 - Fault reset if an active fault exists. Proceed to SWITCH-ON
INHIBITED.
Note: This bit is effective only if the fieldbus interface is set as
the source of the reset signal by drive parameters.
0 - Continue normal operation.
8 (Inching 1)
1 - Accelerate to inching (jogging) setpoint 1.
Notes: Bits 4…6 must be 0.
0 - Inching (jogging) 1 disabled.
9 (Inching 2)
1 - Accelerate to inching (jogging) setpoint 2. See notes at bit 8.
0 - Inching (jogging) 2 disabled.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...