Startup Assistant & Parameters 12-55
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
STANDARD AI
(Continued)
AI2 UNIT SELECTION
(12.25)
Default: mA
Range: V or mA
V
Volts
mA Milliamperes
Selects the unit for readings and settings related to analog input AI2.
Note:
This setting must match the corresponding hardware setting on
the drive control unit (see the hardware manual of the drive).
Control board reboot (either by cycling the power or through
parameter 96.08 Control board boot) is required to validate any
changes in the hardware settings.
AI2 FILTER TIME
(12.26)
Default: 0.100 s
Range: 0.000 - 30.000 s
Defines the filter time constant for analog input AI2. See parameter
12.16 AI1 filter time.
AI2 MIN
(12.27)
Default: 0.000mA or V
Range: -22.000 to +22.000mA or V
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal from
plant is wound to its minimum setting.
See also parameter 12.01 AI tune.
AI2 MAX
(12.28)
Default: 20.000mA or 10.000V
Range: -22.000 to +22.000mA or V
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal from
plant is wound to its maximum setting.
See also parameter 12.01 AI tune.
AI2 SCALED AT AI2 MIN
(12.29) Default: 0.000
Range: -32768.000 to +32767.000
Defines the real value that corresponds to the minimum analog input
AI2 value defined by parameter 12.27 AI2 min. (Changing the polarity
settings of 12.29 and 12.30 can effectively invert the analog input.)
12.30
12.28
12.27
12.29
AI
in
(
12.21
)
AI
scaled
(
12.22
)
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...