12-54 Startup Assistant & Parameters
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
STANDARD AI
(Continued)
AI1 MIN
(12.17)
Default: 0.000mA or V
Range: -22.000 to +22.000mA or V
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal from
plant is wound to its minimum setting.
See also parameter 12.01 AI tune.
AI1 MAX
(12.18)
Default: 20.000mA or 10.000V
Range: -22.000 to +22.000mA or V
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal from
plant is wound to its maximum setting.
See also parameter 12.01 AI tune.
AI1 SCALED AT AI1 MIN
(12.19) Default: 0.000
Range: -32768.000 to +32767.000
Defines the real internal value that corresponds to the minimum analog
input AI1 value defined by parameter 12.17 AI1 min. (Changing the
polarity settings of 12.19 and 12.20 can effectively invert the analog
input.)
12.20
12.18
12.17
12.19
AI
in
(
12.11
)
AI
scaled
(
12.12
)
AI1 SCALED AT AI1 MAX
(12.20)
Default: 1500.000; 1800.000 (95.20 b0)
Range: -32768.000 to +32767.000
Defines the real internal value that corresponds to the maximum
analog input AI1 value defined by parameter 12.18 AI1 max. See the
drawing at parameter 12.19 AI1 scaled at AI1 min.
AI SUPERVISION SELECTION
(12.21)
Default:
Read Only
Range: -22.000 to +22.000mA or V
Displays the value of analog input AI2 in mA or V (depending on
whether the input is set to current or voltage by a hardware setting).
This parameter is read-only.
AI2 SCALED VALUE
(12.22)
Default:
Read Only
Range: -32768.000 to +32767.000
Displays the value of analog input AI2 after scaling. See parameters
12.29 AI2 scaled at AI2 min and 12.30 AI2 scaled at AI2 max.
This parameter is read-only.
Содержание ACS880+N5350
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Страница 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Страница 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Страница 201: ...B 2 Dimensions 3AXD50000011888 Figure B 1 Frame R1 IP21 UL Type 1 Frame R1 IP21 UL Type 1 3AUA0000097621 ...
Страница 202: ...Dimensions B 3 3AXD50000011888 Figure B 2 Frame R2 IP21 UL Type 1 Frame R2 IP21 UL Type 1 3AUA0000097691 ...
Страница 203: ...B 4 Dimensions 3AXD50000011888 Figure B 3 Frame R3 IP21 UL Type 1 Frame R3 IP21 UL Type 1 3AUA0000097847 ...
Страница 206: ...Dimensions B 7 3AXD50000011888 Figure B 6 R6 IP21 UL Type 1 Frame R6 IP21 UL Type 1 3AUA0000098321 ...
Страница 207: ...B 8 Dimensions 3AXD50000011888 Figure B 7 Frame R7 IP21 UL Type 1 Frame R7 IP21 UL Type 1 3AUA0000073149 ...
Страница 208: ...Dimensions B 9 3AXD50000011888 Figure B 8 Frame R8 IP21 UL Type 1 Frame R8 IP21 UL Type 1 3AUA0000073150 ...
Страница 209: ...B 10 Dimensions 3AXD50000011888 Figure B 9 Frame R9 IP21 UL Type 1 Frame R9 IP21 UL Type 1 3AUA0000073151 ...
Страница 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Страница 212: ...CE Guidelines C 3 3AXD50000011888 ...
Страница 244: ...Ethernet IP Setup G 3 3AXD50000011888 3 Click on New Module 4 Select Module Type ETHERNET MODULE ...
Страница 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...