Parameters
Group 53: FBA Data Out
Group 58: Drive EFB
The drive's Group 58 must be replicated on bypass, since the EFB link on the drive
is reserved for internal communication with the bypass. All Group 58 functionality
associated with selection by 98.02 is hosted on the bypass controller for drive.
Group 58 parameters on the bypass are a subset of the Group 58 parameters on the
drive.
Group 53: FBA Data Out
Code
Name
Resolution
Range
Default
Description
5301
...
5310
DATA OUT 1
...
DATA OUT10
1
0 = Not In Use
1 = Control Word (ABBDP)
2 = Ref 1 (ABBDP)
3 = Ref 2 (ABBDP)
4 = Status Word (ABBDP)
5 = Actual Value 1 (ABBDP)
6 = Actual Value 2 (ABBDP)
0101h -063FFh = Drive
parameters
8101h - E3FFh = Bypass
para 8000h
—
Specifies information to be
written to the drive (out of
the network). Only for
modules that support the
cyclic low scanner function
(such as FMBT-12).
For specifying values 1-6,
select ABB drive’s profile
information, like control
word of reference.
To specify drive
parameters, use the format
ggh.pph where gg
h
is the
parameter group in
hexadecimal and pp
h
is the
parameter in hexadecimal.
For instance, drive
parameter 30.14 is
encoded as 1E0Eh.
Bypass parameter is
specified as 8000h +
gg
h
.pp
h
. For instance,
bypass parameter 0114 is
encoded as 810Eh.
Group 58: Drive EFB
Code
Name
Resolution
Range
Default
Description
5802
DV PROT ID
hex
0x0000 - 0xFFFF
0x0000
Protocol ID and revision:
Format:
XXYY where XX = protocolID and
YY = program revision
5803
DV MAC ID
1
0 - 65535
256
Default value is protocol-
dependent: Modbus and N2 is 1,
BACnet is 128. Drive station ID
(NODE ADDRESS)
Refer to
on page
information.
5804
BAUD RATE
0.1 kbit/s
1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6, 76.8
9.6
Default value is protocol-
dependent: Modbus and N2 is
9.6, BACnet is 38.4. Defines the
communication speed of the
RS485 link in kbits per second
(kb/s).
Refer to
on page
information.
5805
EFB PARITY
1
0=8 NONE 1,
1=8 NONE 2,
2=8 EVEN 1,
3=8 ODD 1
0
Defines the data length, parity and
stop bits to be used with the
RS485 link communication.
Default value is protocol-
dependent: Modbus is 1, N2 and
BACnet is 0. Refer to
on
page
for more information.
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......