ACH580 E-Clipse bypass and packaged drive user manual
143
Embedded fieldbus
attempt to read or write outside the parameter addresses, the Modbus interface
returns an exception code to the controller.
• Register addressing is done as follows:
– For drive parameters use: 256 * parameter group + parameter index.
For example: parameter 22.80 would be mapped to register 256 *
22 + 80 = 405712.
– For bypass parameters use: 256 * (parameter group + 128) +
parameter index.
For example: bypass parameter 01.11 would be mapped to register
256 * (1 + 128) + 11 = 433035.
The following table summarizes the 4xxxxx drive control registers 400001…400099
(for 4xxxxx registers above 400099, see the drive parameter list, e.g. 400258 is
parameter 0102):
Modbus Register
Access
Remarks
4
00001
ABB DRIVES
PROFILE CONTROL
WORD
R/W
Maps directly to the profile’s Control Word. Supported
only if bypass parameter 5825 = 0 or 2 (ABB drive
profile). Bypass parameter 5318 holds a copy in hex
format.
4
00002
Reference 1
R/W
Range = 0...+20000 (scaled to +maximum reference),
or -20000...0 (scaled to -maximum reference). Where:
maximum reference is drive parameter 46.01, Speed
scaling if control mode is vector or parameter 46.02,
Frequency scaling if control mode is scalar.
4
00003
Reference 2
R/W
Range = 0...+10000 (scaled to +maximum reference),
or -10000...0 (scaled to -maximum reference). Where:
maximum reference is drive parameter 46.01, Speed
scaling if control mode is vector or parameter 46.02,
Frequency scaling if control mode is scalar.
4
00004
ABB DRIVES
PROFILE STATUS
WORD
R
Maps directly to the profile‘
S
STATUS WORD.
Supported only if bypass parameter 5825 = 0 or 2 (ABB
bypass profile). Bypass parameter 5819 holds a copy in
hex format.
4
00005
1
Actual 1.
(select using drive
parameter 58.28,
EFB act1 type)
R
By default, stores a copy of speed or frequency. Use
drive parameter 58.28 to select a different value.
4
00006
2
Actual 2.
(select using drive
parameter 58.29,
EFB act2 type)
R
By default, stores nothing. Use drive parameter 58.29
to select a value.
4
00007
Actual 3.
(select using bypass
parameter 58107)
R
By default, stores nothing. Use bypass parameter 5312
to select an actual value for this register.
4
00008
Actual 4.
(select using bypass
parameter 58108)
R
By default, stores nothing. Use bypass parameter 5313
to select an actual value for this register.
4
00009
Actual 5.
(select using bypass
parameter 58109)
R
By default, stores nothing. Use bypass parameter 5314
to select an actual value for this register.
4
00010
Actual 6.
(select using bypass
parameter 58110)
R
By default, stores nothing. Use bypass parameter 5315
to select an actual value for this register.
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......