128
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
Note:
For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
Analog output object instance summary – Drive
The following table summarizes the Analog Output Objects supported:
Note:
For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
Name
Description
BACnet
Access Point
Mailbox Parameter
Enter the number of the drive group and parameter number
using the format: (group #) * 256 + parameter #.
Example: drive parameter 28.01 is entered as (28 * 256)
+ 1 = 7169
AV25
Mailbox Data
Contains the parameter value after a read, or enter the
desired parameter value for a write.
AV26
Mailbox Read
A binary value triggers a read – the value of the “Mailbox
Parameter” appears in “Mailbox data”.
BV15
Mailbox Write
A binary value triggers a write – the drive value for the
“Mailbox Parameter” changes to the value in “Mailbox data”.
BV16
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......