ACH580 E-Clipse bypass and packaged drive user manual
147
Embedded fieldbus
1
OFF2
CONTROL
1
OPERATING
Continue operation (OFF2 inactive)
0
EMERGENCY
OFF
Drive coasts to stop.
Normal command sequence:
• Enter OFF2 ACTIVE
• Proceed to SWITCHON INHIBITED
2
OFF3
CONTROL
1
OPERATING
Continue operation (OFF3 inactive)
0
EMERGENCY
STOP
Drive stops within in time specified by
drive parameter 23.23.
Normal command sequence:
• Enter OFF3 ACTIVE
• Proceed to SWITCH ON INHIBITED
WARNING!
Be sure motor and bypass
equipment can be stopped using this
mode.
3
INHIBIT
OPERATION
1
OPERATION
ENABLED
Enter OPERATION ENABLED
(Note the
Run Permissive signal must be active.
See bypass parameter 1601. If 1601 is set
to COMM, this bit also actives the Run
Permissive signal.)
0
OPERATION
INHIBITED
Inhibit operation. Enter OPERATION
INHIBITED
4
Unused (
ABB DRV LIM
)
RAMP_OUT_
ZERO
(ABB DRV
FULL)
1
NORMAL
OPERATION
Enter RAMP FUNCTION GENERATOR:
ACCELERATION ENABLED
0
RFG OUT ZERO
Force ramp function generator output to
Zero. Drive ramps to stop (current and DC
voltage limits in force).
5 RAMP_HOLD
1
RFG
OUT
ENABLED
Enable ramp function.
Enter RAMP FUNCTION GENERATOR:
ACCELERATOR ENABLED
0
RFG OUT HOLD
Halt ramping (Ramp Function Generator
output held)
6
RAMP_IN_
ZERO
1
RFG INPUT
ENABLED
Normal operation. Enter OPERATING
0
RFG INPUT ZERO
Force Ramp Function Generator input to
zero.
7
RESET
0=>1
RESET
Fault reset if an active fault exists (Enter
SWITCH-ON INHIBITED). Effective if
bypass parameter 1604 = COMM.
0
OPERATING
Continue normal operation
8…9
Unused
ABB Drives Profile (EFB) CONTROL WORD
Bit
Name
Value
Commanded
State
Comments
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......