ACH580 E-Clipse bypass and packaged drive user manual
55
Application macros
Smoke Control (Override1) macro
*
Smoke Control (Override1) is a fixed input. Closing Digital Input 6
will
place the E-Clipse Bypass in Automatic
Smoke Control mode. The Macro change will be implemented when DI6 closes. All Interlock and Permissives
are required before the motor runs. Refer to the Smoke Control (Override1) documentation.
Parameter Number
Description
Setting
1602
Damper End Switch
PERMISSIVE
DI2
1603
High Pressure Switch, High Priority Safeties
INTERLOCK 1
DI3
1604
Supply Smoke Detector, Emergency Shutdown
INTERLOCK 2
DI4
1605
Freezestat, Low Priority Safeties
INTERLOCK 3
DI5
Speed Reference / Process Setpoint
Process Feedback Signal
ACH580 CONTROL BOARD
E-CLIPSE BYPASS CONTROL BOARD
Terminal for Signal Cable Shield
Analog Input Common
Analog Input 2
10V / 10mA Reference Voltage for Potentiometer
Analog Input Common
Analog Input 1
X1
1
1
5
4
3
2
6
2
5
4
3
6
7
10
9
8
11
X2
25
23
22
21
20
24
19
18
17
16
15
14
13
12
+24VDC
+24VDC
Digital Input Common
GND
Digital Input 1 (Parameter 1601)
START/STOP
Digital Input 2 (Parameter 1602)
RUN PERMISSIVE
Digital Input 3 (Parameter 1603)
INTERLOCK 1
Digital Input 4 (Parameter 1604)
Digital Input 5 (Parameter 1605)
INTERLOCK 3
Digital Input 6 (Fixed)
SMOKE CONTROL* (Override 1)
Relay Output 1
(Parameter 1401)
BYP NOT FLT
Default Operation: Bypass Not Faulted 11 connected to 13
Bypass Faulted 11 connected to 12
Relay Output 2
(Parameter 1404)
SYS RUNNING
Default Operation: System Running
14 connected to 16
Relay Output 3
(Parameter 1407)
SYS STARTED
Default Operation: System Started
17 connected to 19
Relay Output 4
(Parameter 1410)
BYPASS SEL
Default Operation: Bypass Selected
20 connected to 22
Relay Output 5
(Parameter 1413)
BYPASS AUTO
Default Operation: Bypass In Auto
23 connected to 25
Fire Shutdown & Customer Auto Start
High Static Switch
X2
Freezestat & Return SD
Damper End Switch
To Damper Actuator
INTERLOCK 2
Automatic Smoke Control
Manual Smoke Control & Supply SD
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......