ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
AV13
EXT PID DEV
This object is the External PID output
signal’s deviation from its setpoint.
Calculated as (drive parameter 71.04) /
drive parameter 71.14).
Percent
R
AV14
RUN TIME (R)
This object indicates, in hours, the drive’s
accumulated run time since the last reset.
The value can be reset to zero. The
corresponding drive parameter is 05.03.
Hours
W
AV15
MOTOR TEMP
This object indicates the drive’s motor
temperature, as set up in parameter
Group 35. The corresponding drive
parameter is 35.02 or 35.03 if either
enabled or 35.01.
°C
R
AV16
INPUT REF 1
This object sets 03.09. Group 22 must be
configured to make use of EFB ref 1.
Percent
C
AV17
INPUT REF 2
• This object sets 03.10. Group 22 must
be configured to make use of EFB
ref 2.
Percent
C
AV18
LAST FLT
This object indicates the most recent fault
entered in the drive’s fault log.
None
R
AV19
PREV FLT 1
This object indicates the second most
recent fault entered in the drive’s fault
log.
None
R
AV20
PREV FLT 2
This object indicates the third most recent
fault entered in the drive’s fault log.
None
R
AV21
AO 1 ACT
This object indicates Analog Output 1’s
level. The corresponding drive parameter
is 12.11. Units depend on drive
parameter 12.15.
mA or V
R
AV22
AO 2 ACT
This object indicates Analog Output 2’s
level. The corresponding drive parameter
is 12.22. Units depend on drive
parameter 12.25.
mA or V
R
AV23
ACCEL1 TIME
This object sets the Ramp1 acceleration
time. The corresponding drive parameter
is 28.72 if 99.04 value = Scalar; 23.12 if
99.04 value = Vector.
Seconds
W
AV24
DECEL1 TIME
This object sets the Ramp1 deceleration
time. The corresponding drive parameter
is 28.73 if 99.04 value = Scalar; 23.13 if
99.04 value = Vector.
Seconds
W
AV25
MBOX PARAM
This object defines the parameter to be
read or written to by the mailbox function.
See BV15 and BV16.
None
W
AV26
MBOX DATA
This object holds the mailbox function’s
parameter value – a value that was read,
or is to be written. See BV15 and BV16.
None
W
AV29
FRQ OUT MIN
This object indicates the drive’s minimum
output frequency.
Amps
R
AV30
FRQ OUT MAX
This object indicates the drive’s
maximum output frequency.
Percent
R
Instance
ID
Object Name
Description
Units
Present Value
Access Type
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......