ACH580 E-Clipse bypass and packaged drive user manual
155
Embedded fieldbus
Modbus protocol technical data - system mode
Bypass overview
The new mode that is available on the E-Clipse bypass is selected by setting bypass
parameter 1625 to SYSTEM. With this configuration the drive node is still present
but network commands to start the drive are ignored. Instead, the user should send
start commands to the bypass node. In this mode, a start command will start the
bypass if in bypass mode or start the drive if in drive mode.
In system mode, the profile that controls system logic is always the ABB BYPASS
PROFILE which is sent to the bypass device. The setting of bypass parameter 5825,
PROFILE is only used for reference related control (e.g. ramp control bits) and for
the drive status word. These bits are used when writing to or reading the drive
device.
The following table defines the ABB bypass profile control word. Note that this word
is written to the bypass.
ABB Bypass Profile
CONTROL
WORD
Bit
Name
Value
Description
Comments
0
START
1
Start
0
Stop
1
RESET
0->1
Reset command
Fault reset. Edge sensitive.
Other
(no op)
2
RUN_DISABLE
1
Run disabled
Inverted Run Permissive. The
STARTED status bit may be set even
when Run Permissive is missing.
0
Run Permissive on
3
FBLOCAL_CTL
1
FB Local mode for
control word
requested
Field bus sets these bits to move the
bypass to field bus local control mode
of control word (field bus steals the
control).
0
FB Local mode for
control word not
requested
4
START_DISABLE1
1
Start disabled 1
Inverted Start Interlocks. When Start
Interlock is missing, the drive doesn’t
set STARTED status bit.
0
Start Interlock 1 on
5 START_DISABLE2
1
Start
disabled
2
0
Start Interlock 2 on
6
START_DISABLE3
1
Start disabled 3
0
Start Interlock 3 on
7
START_DISABLE4
1
Start disabled 4
0
Start Interlock 4 on
8
OVERRIDE
1
Override selected
This selects override 2 which is
controlled by Group 17.
0
Override not
selected
9
LINK_ON
1
Master is detected
in link
This is not settable from the field bus
but reflects the internal state of the link.
0
Link is down
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......