Installation
Motor connections
Connect the motor cables to the output terminal block as shown on page
. Also
see
Connection and wiring diagrams – Box E-Clipse Bypass
on page
. The motor
grounding conductor can be connected to the ground lug near the terminal block.
Note:
Route cables through the cable guides on the left side of the enclosure. Use
separate conduits for input power and motor cables. Follow the guides to separate
the cables from each other.
WARNING!
Check the motor and motor wiring insulation before connecting the
ACH580 to line power. Refer to the
ACH580-01 Hardware Manual
(3AXD50000044839). Before proceeding with the insulation resistance
measurements, check that the ACH580 is disconnected from incoming line power.
Failure to disconnect line power could result in death or serious injury.
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......