104
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
N2 binary input objects – Drive
The following table lists the N2 Binary Input objects defined for the ACH580 drive.
AI14
PRC PID DEVIATION
40.99
0.1
%
0…100
AI15
EXT PID FEEDBACK
Derived value
0.1
%
0…100
AI16
EXT PID DEVIATION
Derived value
0.1
%
0…100
AI17
LAST FAULT
Derived value
1
fault code
AI18
PREV FAULT
Derived value
1
fault code
AI19
OLDEST FAULT
Derived value
1
fault code
AI20
AI 1 ACTUAL
12.101
0.1
%
0…100
AI21
AI 2 ACTUAL
12.102
0.1
%
0…100
AI22
AO 1 ACTUAL
13.11
0.1
mA
0…20
AI23
AO 2 ACTUAL
13.21
0.1
mA
0…20
AI24
MOTOR TEMP
Derived value
1
°
C
0…200
1) Rated Speed Is A Percent Of Maximum Frequency (Parameter 2008) If The Drive Is In Scalar
Mode, And Is A Percent Of Maximum Speed (Parameter 2002) In Speed Mode.
N2 Binary Inputs:
Number
Object
Drive Parameter
Range
BI1
STOP/RUN
Status Word, BIT2
0 = Stop, 1 = Drive Running
BI2
FORWARD/REVERSE
Status Word, BIT11
0 = Forward, 1 = Reverse
BI3
FAULT STATUS
Status Word, BIT15
0 = OK, 1 = Drive Fault
BI4
RELAY 1 STATUS
10.21, BIT0
0 = Off, 1 = On
BI5
RELAY 2 STATUS
10.21, BIT1
0 = Off, 1 = On
BI6
RELAY 3 STATUS
10.21, BIT2
0 = Off, 1 = On
BI7
RELAY 4 STATUS
15.04, BIT0
0 = Off, 1 = On
BI8
RELAY 5 STATUS
15.04, BIT1
0 = Off, 1 = On
BI9
DIGITAL OUT 1 STATUS
15.04, BIT5
0 = Off, 1 = On
BI10
INPUT 1 STATUS
10.02, BIT0
0 = Off, 1 = On
BI11
INPUT 2 STATUS
10.02, BIT1
0 = Off, 1 = On
BI12
INPUT 3 STATUS
10.02, BIT2
0 = Off, 1 = On
BI13
INPUT 4 STATUS
10.02, BIT3
0 = Off, 1 = On
BI14
INPUT 5 STATUS
0119 (bit mask 02)
0 = Off, 1 = On
BI15
INPUT 6 STATUS
10.02, BIT5
0 = Off, 1 = On
BI16
EXTERNAL 2 SELECT
DCU status word, BIT14 0 = EXT1 = EXT2
BI17
HAND/AUTO
DCU status word, BIT12 0 = AUTO, 1 = HAND
BI18
WARNING
DCU status word, BIT16 0 = OK, 1 = WARNING
BI20
DRIVE READY
DCU status word
,
BIT0
0 = Not Ready, 1 = Ready
BI21
AT SETPOINT
DCU status word, BIT7
0 = No, 1 = At Setpoint
N2 Analog Inputs:
Number
Object
Drive
Parameter
Resolution
Units
Range
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......