ACH580 E-Clipse bypass and packaged drive user manual
65
Parameters
1616
DISP WRNGS
1
0 = DISABLE
1 = ENABLE
ENABLE
(1)
Enables warnings to be
displayed:
INP PHASE A LOSS,
INP PHASE B LOSS,
INP PHASE C LOSS,
MTR OVERLOAD,
BYPASS DISABLED,
DRIVE SETUP,
PCB TEMP
DRIVE LINK ERROR
DRIVE FAULTED
1617
DRIVE TEST
1
0 = DISABLE
1 = ENABLE
DISABLE
(0)
Enables drive test mode. Drive
contactor is opened.
1618
PASS CODE
1
0 - 65535
123
Pass code entry to edit panel
lock parameter and view/edit
security lock parameters. The
security parameters are
1640 – 1644. Default: 123
1619
PAR LOCK
1
0 = LOCKED
1 = OPEN
OPEN
(1)
When switched to "LOCKED"
prevents parameter changes
from panel. Does not affect to
Field Bus writes, expect
changing the lock value itself:
correct password must always
be set first, even in case of Field
Bus.
1620
PERMSV TXT
1
0 = PERMISSIVE
1 = DAMPER
END SWTCH
2 = VALVE
OPENING
3 = PRE-LUBE
CYCLE
PERMISSIVE
(0)
Alternative text choices for
warning 4006.
1621
INTLK1 TXT
1
0 = INTERLOCK 1
1 = VIBRATION
SWITCH
2 = FIRESTAT
3 = FREEZESTAT
4 =
OVERPRESSUR
E
5 = VIBRATION
TRIP
6 = SMOKE
WARNING
7 = SAFETY
OPEN
8 = LOW
SUCTION
INTERLOCK 1
(0)
Alternative text choices for
warning 4021.
1622
INTLK2 TXT
1
0 = INTERLOCK 2
...
INTERLOCK 2
(0)
Alternative text choices for
warning 4022.
See parameter 1621 for range.
1623
INTLK3 TXT
1
0 = INTERLOCK 3
...
INTERLOCK 3
(0)
Alternative text choices for
warning 4023.
See parameter 1621 for range.
1624
INTLK4 TXT
1
0 = INTERLOCK 4
...
INTERLOCK 4
(0)
Alternative text choices for
warning 4024.
See parameter 1621 for range.
1625
COMM CTRL
1
0 = DRIVE ONLY
1 = SYSTEM
DRIVE ONLY
(0)
Selects comm control mode. In
drive only mode, control of drive
is made through drive points,
and control of bypass over
comms is not possible. In
system mode, control of system
(bypass or drive) is made
through bypass points.
Group 16: System Control
Code
Name
Resolution
Range
Default
Description
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......