168
ACH580 E-Clipse bypass and packaged drive user manual
Fieldbus adapter
Drive relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
Note:
Relay status feedback occurs without configuration as defined below.
Drive Parameter
Value
Description
Protocol Reference
Modbus TCP
ABB DRV
DCU PROFILE
10.24
RO1
Source
Relay Output 1
62, RO/DIO
control
word
Relay Output 1
controlled by fieldbus.
402659 bit 0 or 00033
10.27
Relay Output 2
Relay Output 2
controlled by fieldbus.
402659 bit 1 or 00034
10.30
Relay Output 3
Relay Output 3
controlled by fieldbus.
402659 bit 2 or 00035
15.07
1
Relay Output 4
Relay Output 4
controlled by fieldbus.
402659 bit 3 or 00036
15.10
1
Relay Output 5
Relay Output 5
controlled by fieldbus.
402659 bit 4 or 00037
15.23
1
DO1
Source
Digital Output 1
Digital Output 1
controlled by fieldbus.
402659 bit 8 or 00038
1) More than 3 relays requires the addition of a relay extension module.
Drive Parameter
Value
Protocol Reference
Modbus TCP
ABB DRV
DCU PROFILE
10.21 RO Status
RO 1-3 STATUS
Relay 1…3 status.
402581 or 00033...35
15.04 RO/DO Status
RO 4-6 STATUS
Relay 4…6 status.
403844 or 00036...37
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......