ACH580 E-Clipse bypass and packaged drive user manual
171
Fieldbus adapter
Start/stop direction control
Using the fieldbus for start/stop control of the system requires:
• Bypass parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Miscellaneous system control
Note:
Control of system commands is dependent upon the setting of bypass
parameter 1625.
Using the fieldbus miscellaneous system control requires:
• Bypass parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Bypass Parameter
Value
Description
Protocol Reference
Modbus TCP
1
ABB DRV
DCU PROFILE
1601
START/STOP
2 (COMM)
Start/Stop by fieldbus with
Ext1 or Ext2 selected.
400001 bits
0…3
40031 bits 0, 1
1625
COMM CTRL
1 (SYSTEM) Enable system control.
N/A
1) For Modbus TCP, the protocol reference can depend on the profile used, hence two columns in
these tables. One column refers to the ABB Drives profile, selected when parameter 51.02 = 0
(ABB Drives-Classic) or 51.02 = 1 (ABB Drives-Enhanced). The other column refers to the DCU
profile selected when parameter 51.02 = 2 (Transparent-16-Bit). See
section on page
Bypass Parameter
Value
Setting
Protocol
Reference
Modbus TCP
1602
RUN PERMISSIVE
2 (COMM)
(Not Recommended)
Run permissive by
fieldbus.
400001 bit 2
1603
START INTERLOCK 1
2 (COMM)
(Not Recommended)
Source for Start
Interlock 1 is the
fieldbus Command
word.
400001 bit 4
1604
START INTERLOCK 2
2 (COMM)
(Not Recommended)
Source for Start
Interlock 2 is the
fieldbus Command
word.
400001 bit 5
1605
START INTERLOCK 3
2 (COMM)
(Not Recommended)
400001 bit 6
1606
START INTERLOCK 4
2 (COMM)
(Not Recommended)
400001 bit 7
1607
START RESET SEL
2 (COMM)
Fault reset by fieldbus
400001 bit 1
1625
COMM CTROL
1 (SYSTEM)
Enable System Control. N/A
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......