144
ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
For the Modbus protocol, drive parameters in group 58 report the parameter
mapping to 4xxxxx Registers.
4
00011
Actual 7.
(select using bypass
parameter 58111)
R
By default, stores nothing. Use bypass parameter 5316
to select an actual value for this register.
4
00012
Actual 8.
(select using bypass
parameter 58112)
R
By default, stores nothing. Use bypass parameter 5317
to select an actual value for this register.
4
00031
DCU CONTROL
WORD LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile’s
CONTROL
WORD
. Supported only if BP Param
5825 = 1. See bypass parameter 0301.
4
00032
DCU CONTROL
WORD MSW
R
Maps directly to the Most Significant Word of the DCU
profile’s
CONTROL
WORD
. Supported only if BP Param
5825 = 1. See bypass parameter 0302.
4
00033
DCU STATUS
WORD LSW
R
Maps directly to the Least Significant Word of the DCU
profile’s
CONTROL
WORD
. Supported only if BP Param
5825 = 1. See bypass parameter 0303.
4
00034
DCU STATUS
WORD MSW
R
Maps directly to the Most Significant Word of the DCU
profile’s
CONTROL
WORD
. Supported only if BP Param
5825 = 1. See bypass parameter 0304.
400045
ACH580 REF1 LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile’s
REF
1. Supported only if BP Parameter
5825 = 1. See drive parameter 03.09, EFB reference 1.
400046
ACH580 REF1 MSW
R/W
Maps directly to the Most Significant Word of the DCU
profile’s
REF
1. Supported only if BP Parameter
5825 = 1. See drive parameter 03.09, EFB reference 1.
400047
ACH580 REF2 LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile’s
REF
2. Supported only if BP Parameter
5825 = 1. See drive parameter 03.10, EFB reference 2.
400048
ACH580 REF2 MSW
R/W
Maps directly to the Most Significant Word of the DCU
profile’s
REF
2. Supported only if BP Parameter
5825 = 1. See drive parameter 03.10, EFB reference 2.
1) These Modbus Register numbers are selected using drive parameters 58.28 and 58.29.
2) These Modbus Register numbers are selected using drive parameters 58.28 and 58.29.
BP Param
Description
58107
DV IO 7
Specifies the parameter mapped to Modbus register 400007.
58108
DV IO 8
Specifies the parameter mapped to Modbus register 400008.
58109
DV IO 9
Specifies the parameter mapped to Modbus register 400009.
58110
DV IO 10
Specifies the parameter mapped to Modbus register 400010.
58111
DV IO 11
Specifies the parameter mapped to Modbus register 400011.
58112
DV IO 12
Specifies the parameter mapped to Modbus register 400012.
5318
Reserved.
Modbus Register
Access
Remarks
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......