186
ACH580 E-Clipse bypass and packaged drive user manual
Diagnostics
Correcting faults
The recommended corrective action for faults is:
• Use the following
table to find and address the root cause of the
problem.
• Reset the system.
Fault listing
Fault
Code
Fault Name
In Panel
Fault
Possible Cause
Corrective Action
3001
COIL CURR
FBK
RBCU is sensing
abnormal current
feedback when neither
contactor should be
energized
Defective component
on RBCU
Change RBCU
3002
BYP CNTACT
STUCK
M2 contactor indicates it
is not prepared to move
on a power up check of
the contactor or after
contact is commanded
to open
Defective Contactor
Defective RBCU
Disconnect incoming power
from unit
Check if contactor armature
moves freely. If armature
moves freely, then change the
RBCU. If armature does not
move freely, then change
individual contactor (M2) or
the complete assembly
(RCSA-0x)
3003
DRV CNTACT
STUCK
M1 contactor indicates it
is not prepared to move
on a power up check of
the contactor or after
contact is commanded
to open
Defective Contactor
Defective RBCU
Disconnect incoming power
from unit
Check if contactor armature
moves freely. If armature
moves freely, then change the
RBCU. If armature does not
move freely, then change
individual contactor (M1) or
the complete assembly
(RCSA-0x)
3004
BYPASS
COIL OPEN
M2 contactor will not
close when commanded
to do so
Loose J8 connector
on RBCU
Loose wires on
contactor terminals
A1 and/or A2
Bad Output on
RBCU
Bad Contactor
Verify that J8 connector is
firmly seated.
With incoming power
disconnected, check for
tightness of A1 and A2
terminals
Swap RBCU
Change Contactor/Assembly
3005
DRIVE COIL
OPEN
M1 contactor will not
close when commanded
to do so
Loose J8 connector
on RBCU
Loose wires on
contactor terminals
A1 and/or A2
Bad Output on
RBCU
Bad Contactor
Verify that J8 connector is
firmly seated.
With incoming power
disconnected, check for
tightness of A1 and A2
terminals
Swap RBCU
Change Contactor/Assembly
Содержание ACH580 Series
Страница 2: ......
Страница 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Страница 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Страница 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Страница 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Страница 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Страница 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Страница 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Страница 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Страница 256: ......