72
Cooling Circuit
3.9 Scroll Stand-by
Compressor
3.9
Scroll Stand-by Compressor
Scroll Compressor ensure cooling operation during Stand-by mode. Compressor operativity is provided with liquid injection
that protect compressor from overheating during operation.
Specifications
Unit Compressor
un0°060 ZF11
un0°080 ZF13
un0°100 ZF15
un0°120 ZF18
CAUTION
!
Check compressor tension is in
accordance with unit one.
Valve Specifications:
Opening Set Point: 116°C ± 3°C(193°F ± 5°F )
Liquid Line Connection: 9, 5mm (3”)
Maximum operating temperature of sensing bulb is limited
to 145°C (293°F ).
Individual Protection Devices
Shoes, Goggles, Gloves
Injection valve replacement
(a)
Pump down unit.
(b)
Disconnect Unit from Electrical
Supplies (Battery and Electrical
Main).
(c)
Close compressors suction valves.
(d)
Purge from LP service port.
Summary of Contents for un0 010
Page 1: ...0MAN295 USA WORKSHOPMANUAL un0...
Page 4: ......
Page 15: ......
Page 16: ......
Page 17: ...Section1 Generalinformation...
Page 19: ......
Page 30: ......
Page 31: ...Section2 Descriptionoftheunit...
Page 33: ......
Page 45: ...34 Description of the unit 2 2 Evaporating section...
Page 46: ......
Page 47: ...Section3 CoolingCircuit...
Page 94: ......
Page 95: ...Section4 DieselEngine...
Page 97: ......
Page 130: ......
Page 131: ...Section5 ElectronicsandWirings...
Page 135: ......
Page 146: ...135 5 2 Electronic Boards Electronics and wiring 5 2 Electronic Boards CPU board...
Page 150: ...139 5 2 Electronic Boards Electronics and wiring Relay Board...
Page 155: ...144 Electronics and wiring 5 2 Electronic Boards Low Voltage Wirings...
Page 156: ...145 5 2 Electronic Boards Electronics and wiring High Voltage Wirings...
Page 178: ......
Page 179: ...Section6 Alarms Troubleshooting...
Page 181: ......
Page 183: ...172 Alarms Troubleshooting 6 1 StandardAlarms A04 Low Pressure Switch...
Page 184: ...173 6 1 StandardAlarms Alarms Troubleshooting A07 Water Temperature A08 Door Microswitch...
Page 185: ...174 Alarms Troubleshooting 6 1 StandardAlarms A10 Oil Pressure...
Page 186: ...175 6 1 StandardAlarms Alarms Troubleshooting A11 High Pressure...
Page 188: ...177 6 1 StandardAlarms Alarms Troubleshooting A16 Engine Failure...
Page 189: ...178 Alarms Troubleshooting 6 1 StandardAlarms A17 Alternator Failure...
Page 190: ...179 6 1 StandardAlarms Alarms Troubleshooting A18 Water sensor error...
Page 195: ...184 Alarms Troubleshooting 6 3 Troubleshooting Unit does not start after blackout...
Page 196: ...185 6 3 Troubleshooting Alarms Troubleshooting Unit not performing...
Page 197: ......
Page 198: ......
Page 199: ...Annex1 Parameters...
Page 201: ......
Page 208: ......
Page 209: ......