68
Cooling Circuit
3.7 KVC Hot Gas Bypass
Capacity Regulator
(d)
Release KVC valve from fixing brackets and remove all of which.
(e)
Flux nitrogen (approx. 0, 35barg) from LP service port, to prevent dirt and oxidation during welding
(f)
Fuse with brazer flame KVC welding line and disconnect old valve.
(g)
Clean pipe ends with a special brush and flow with dry nitrogen.
CAUTION
!
Never flow with normal air, it contains too much
humidity.
(h)
Braze KVC valve in position.
CAUTION
!
Wrap KVC valve in a
wet rag, which must be warmer than
ambient avoiding moisture
condensation.
(i)
Reinstall evaporator service ports
valves.
CAUTION
!
Lubricate valve
gaskets before.
(j)
Vacuum unit
3.2.3
Section.
(k)
Connect a vacuum gauge and check for leaks after a waiting time
3.2.5
Section.
(l)
Reinstall valve support brackets.
(m)
Charge unit with refrigerant
3.2.4
Section.
Summary of Contents for un0 010
Page 1: ...0MAN295 USA WORKSHOPMANUAL un0...
Page 4: ......
Page 15: ......
Page 16: ......
Page 17: ...Section1 Generalinformation...
Page 19: ......
Page 30: ......
Page 31: ...Section2 Descriptionoftheunit...
Page 33: ......
Page 45: ...34 Description of the unit 2 2 Evaporating section...
Page 46: ......
Page 47: ...Section3 CoolingCircuit...
Page 94: ......
Page 95: ...Section4 DieselEngine...
Page 97: ......
Page 130: ......
Page 131: ...Section5 ElectronicsandWirings...
Page 135: ......
Page 146: ...135 5 2 Electronic Boards Electronics and wiring 5 2 Electronic Boards CPU board...
Page 150: ...139 5 2 Electronic Boards Electronics and wiring Relay Board...
Page 155: ...144 Electronics and wiring 5 2 Electronic Boards Low Voltage Wirings...
Page 156: ...145 5 2 Electronic Boards Electronics and wiring High Voltage Wirings...
Page 178: ......
Page 179: ...Section6 Alarms Troubleshooting...
Page 181: ......
Page 183: ...172 Alarms Troubleshooting 6 1 StandardAlarms A04 Low Pressure Switch...
Page 184: ...173 6 1 StandardAlarms Alarms Troubleshooting A07 Water Temperature A08 Door Microswitch...
Page 185: ...174 Alarms Troubleshooting 6 1 StandardAlarms A10 Oil Pressure...
Page 186: ...175 6 1 StandardAlarms Alarms Troubleshooting A11 High Pressure...
Page 188: ...177 6 1 StandardAlarms Alarms Troubleshooting A16 Engine Failure...
Page 189: ...178 Alarms Troubleshooting 6 1 StandardAlarms A17 Alternator Failure...
Page 190: ...179 6 1 StandardAlarms Alarms Troubleshooting A18 Water sensor error...
Page 195: ...184 Alarms Troubleshooting 6 3 Troubleshooting Unit does not start after blackout...
Page 196: ...185 6 3 Troubleshooting Alarms Troubleshooting Unit not performing...
Page 197: ......
Page 198: ......
Page 199: ...Annex1 Parameters...
Page 201: ......
Page 208: ......
Page 209: ......