163
5.7 Power Supplies
Electronics and wiring
Rectifier
Function:
Rectifier converts alternating current(AC), which periodically reverses direction, into direct current(DC)
Battery
Specifications:
Tension 12V
Electrical Charge:
100Ah
Function:
Power Cab Command and starting system when unit is turned off.
Alarm:
A15 - Low battery
KSF Phase Sequencer Relay
Function:
Power Cab Command and starting system when unit is turned off.
Specifications:
This device has A and B inside relays.
Contact Status Closing
conditions
7-8
N.O.
V Δ > 320V
12-10
N.C.
L1 − 2 − 3
12-11
N.O.
L1 − 3 − 2
Connections:
Contact Wire
From/to
1
L1
Elc.
Main
3
L2
Elc.
Main
5
L3
Elc.
Main
7
NE1012
J10-12
th
8
93
J8-7
th
10
55
K1
11
56
K2
12
94
FM1
Test:
Connect unit to electrical main and check which contactor, K1 or K2, has been
activated. Disconnect from electrical main and reverse 2 phase wires inside
main plug.
Reconnect and check that active contactor has changed.
Digital Input Label:
Electric Standby Selected
Summary of Contents for un0 010
Page 1: ...0MAN295 USA WORKSHOPMANUAL un0...
Page 4: ......
Page 15: ......
Page 16: ......
Page 17: ...Section1 Generalinformation...
Page 19: ......
Page 30: ......
Page 31: ...Section2 Descriptionoftheunit...
Page 33: ......
Page 45: ...34 Description of the unit 2 2 Evaporating section...
Page 46: ......
Page 47: ...Section3 CoolingCircuit...
Page 94: ......
Page 95: ...Section4 DieselEngine...
Page 97: ......
Page 130: ......
Page 131: ...Section5 ElectronicsandWirings...
Page 135: ......
Page 146: ...135 5 2 Electronic Boards Electronics and wiring 5 2 Electronic Boards CPU board...
Page 150: ...139 5 2 Electronic Boards Electronics and wiring Relay Board...
Page 155: ...144 Electronics and wiring 5 2 Electronic Boards Low Voltage Wirings...
Page 156: ...145 5 2 Electronic Boards Electronics and wiring High Voltage Wirings...
Page 178: ......
Page 179: ...Section6 Alarms Troubleshooting...
Page 181: ......
Page 183: ...172 Alarms Troubleshooting 6 1 StandardAlarms A04 Low Pressure Switch...
Page 184: ...173 6 1 StandardAlarms Alarms Troubleshooting A07 Water Temperature A08 Door Microswitch...
Page 185: ...174 Alarms Troubleshooting 6 1 StandardAlarms A10 Oil Pressure...
Page 186: ...175 6 1 StandardAlarms Alarms Troubleshooting A11 High Pressure...
Page 188: ...177 6 1 StandardAlarms Alarms Troubleshooting A16 Engine Failure...
Page 189: ...178 Alarms Troubleshooting 6 1 StandardAlarms A17 Alternator Failure...
Page 190: ...179 6 1 StandardAlarms Alarms Troubleshooting A18 Water sensor error...
Page 195: ...184 Alarms Troubleshooting 6 3 Troubleshooting Unit does not start after blackout...
Page 196: ...185 6 3 Troubleshooting Alarms Troubleshooting Unit not performing...
Page 197: ......
Page 198: ......
Page 199: ...Annex1 Parameters...
Page 201: ......
Page 208: ......
Page 209: ......