3.3 Valves
Cooling Circuit
(g)
Disconnect 3-way valve from copper tubes with soldering flame.
(h)
Clean pipe ends with a special brush and blow with dry nitrogen.
CAUTION
!
Never blow with normal air, it contains too much
humidity.
(i)
Place new valve in position.
CAUTION
!
Using test coil check valve operativity before.
CAUTION
!
Pay attention to valve flux direction.
(j)
Braze new valve
(k)
Reinstall valve support and clamp valve.
(l)
Vacuum unit.
(m)
Respect a waiting time and check for leaks.
(n)
Charge refrigerant
3.2.4
Section.
(o)
Check defrost operations.
YK Capacity Control Valve Replacement
Capacity control valve is equipped in some
model only, this option helps road starting
operation reducing torque force required from
engine driven alternative compressor.
(a)
Disconnect unit from electrical supplies (Battery and Main).
(b)
Open unit door and right or refrigeration side cover and fold down electrical Box.
(c)
Recover Refrigerant
3.2.2
Section.
Summary of Contents for un0 010
Page 1: ...0MAN295 USA WORKSHOPMANUAL un0...
Page 4: ......
Page 15: ......
Page 16: ......
Page 17: ...Section1 Generalinformation...
Page 19: ......
Page 30: ......
Page 31: ...Section2 Descriptionoftheunit...
Page 33: ......
Page 45: ...34 Description of the unit 2 2 Evaporating section...
Page 46: ......
Page 47: ...Section3 CoolingCircuit...
Page 94: ......
Page 95: ...Section4 DieselEngine...
Page 97: ......
Page 130: ......
Page 131: ...Section5 ElectronicsandWirings...
Page 135: ......
Page 146: ...135 5 2 Electronic Boards Electronics and wiring 5 2 Electronic Boards CPU board...
Page 150: ...139 5 2 Electronic Boards Electronics and wiring Relay Board...
Page 155: ...144 Electronics and wiring 5 2 Electronic Boards Low Voltage Wirings...
Page 156: ...145 5 2 Electronic Boards Electronics and wiring High Voltage Wirings...
Page 178: ......
Page 179: ...Section6 Alarms Troubleshooting...
Page 181: ......
Page 183: ...172 Alarms Troubleshooting 6 1 StandardAlarms A04 Low Pressure Switch...
Page 184: ...173 6 1 StandardAlarms Alarms Troubleshooting A07 Water Temperature A08 Door Microswitch...
Page 185: ...174 Alarms Troubleshooting 6 1 StandardAlarms A10 Oil Pressure...
Page 186: ...175 6 1 StandardAlarms Alarms Troubleshooting A11 High Pressure...
Page 188: ...177 6 1 StandardAlarms Alarms Troubleshooting A16 Engine Failure...
Page 189: ...178 Alarms Troubleshooting 6 1 StandardAlarms A17 Alternator Failure...
Page 190: ...179 6 1 StandardAlarms Alarms Troubleshooting A18 Water sensor error...
Page 195: ...184 Alarms Troubleshooting 6 3 Troubleshooting Unit does not start after blackout...
Page 196: ...185 6 3 Troubleshooting Alarms Troubleshooting Unit not performing...
Page 197: ......
Page 198: ......
Page 199: ...Annex1 Parameters...
Page 201: ......
Page 208: ......
Page 209: ......